From the Boiler Room to the Boardroom: One HVAC Fault, Three Budget Conversations

November 24, 2026

Adapted from the Clockworks webinar for K-12 facilities teams, From the Boiler Room to the Boardroom: Connecting Building Performance to Budget Priorities, with Michael Mandilakis of Gardiner and Thomas Whitlow of Clockworks.

K-12 facilities teams usually know where their buildings are struggling. The harder part is getting the business office, the superintendent, and the board to fund the fix. Michael Mandilakis is Director of Data Services at Gardiner, a building services Clockworks partner serving Ohio and the surrounding states. He showed how his team makes that case with one real fault on one air handler.

“We’ve used one diagnostic. We’ve created three conversations.”

Watch this moment in the webinar — 32:23

The diagnostic comes from Clockworks fault detection and diagnostics (FDD), which reads the data a school’s building automation system (BAS) already produces and turns it into a cause, a cost, and a next step.

Key takeaways

  • A fault can waste money for weeks without setting off a single alarm.
  • One diagnostic gives the facilities team a root cause, the business office a payback, and the superintendent a district-wide case.
  • Every diagnostic is scored from 0 to 10 for energy, comfort, and maintenance, so a small team knows where to start.
  • Gardiner typically goes from first data connection to usable information in about thirty days.
 

The full webinar, “From the Boiler Room to the Boardroom: Connecting Building Performance to Budget Priorities,” with Michael Mandilakis of Gardiner and Thomas Whitlow of Clockworks. The “watch this moment” links below jump this player to the point being quoted.

Why is a K-12 facilities budget so hard to defend?

Thomas Whitlow, enterprise account executive at Clockworks, opened with the pressure districts are under: rising utility costs, a deferred maintenance backlog, and fewer people to do the work. Each group in a district sees that pressure differently. Teachers care about the classroom. The facilities team gets work orders all day. The business office asks what the district can afford, and the superintendent and board answer for the budget.

As Thomas put it, “people buy by committee nowadays”, so a request has to make sense to every one of them. Michael’s answer is to bring the same data to each group.

“It’s much easier to ask for money when you can justify it with data.”

Watch this moment in the webinar — 33:39

What does a costly fault with no alarm look like?

Michael’s example is Air Handler 14 at a high school in the Cleveland area. It is a live diagnostic from a working building. “This is really happening.”

The unit was heating and cooling at the same time. The BAS had told the cooling valve to close, but the air was still getting colder as it passed that coil, which means the valve never closed. To reach its setpoint, the system opened the heating valve to make up the difference. The unit was using two energy sources at once.

The air handler still delivered the 55 degrees it was asked for. Nobody felt a problem and no alarm went off. Clockworks put the waste at $278 over seven days.

“the set point’s met. We don’t necessarily have a comfort issue, but that does not mean that the system is running well.”

Watch this moment in the webinar — 21:35

What does the K-12 facilities team get from the diagnostic?

The facilities team gets the root cause. The diagnostic report states the problem in plain text and lists the likely cause next to it. Here, that was a cooling coil valve that was leaking or stuck open.

“So we’ve gone away from investigating, and we have exactly what we should be looking at.”

Watch this moment in the webinar — 24:38

The team knows which unit and which part to check, and can plan the repair before anyone complains. The report also lists the checks that passed, so the news is not all bad.

One click turns the technical detail into a plain-language summary of what happened, why it was flagged, and what to do. That matters in schools, where the same person may be a roofer one day and a plumber the next. Michael called the tool “a skill gap closer”.

Watch this moment in the webinar — 27:23

What does the business office get?

The business office gets the payback. The same diagnostic shows how much the fault has wasted so far and how much fixing it would save over the next year. No K-12 facilities budget covers everything, so the dollars help decide what comes first.

“instead of having to guess about the impact of the problem, the facility team and the business operations team now both have the information they would need”

Watch this moment in the webinar — 29:06

Michael was clear that some faults will have a low payback. Those are judged on other grounds, like fewer complaints or a better room to learn in.

The same numbers help with a problem many teams know well, a maintenance budget that starts at nothing.

“your budget is zero because you’ve never had the data to explain why it needs to be more than zero.”

Watch this moment in the webinar — 43:55

What does the superintendent get?

The superintendent gets the big picture. The same fault found across several buildings, ranked and added up, becomes savings the district can put toward other priorities.

By the time the request reaches that level, the case for the repair is already built. Michael named three results of finding these faults early. Equipment lasts longer, classrooms see fewer interruptions, and the budget goes further.

Watch this moment in the webinar — 31:33

The history helps with capital planning too. If the team keeps spending time and money on the same unit, the data supports the case to replace it.

How is FDD different from the BAS alarms a district already has?

An audience member asked what to tell someone who is already overwhelmed by BAS alarms. Michael said:

“a BAS alarm is after the problem has already happened.”

Watch this moment in the webinar — 47:49

FDD works ahead of the alarm. It also ranks what it finds. “I have yet to visit a building that was running perfect”, he said, so the first step is deciding what to fix first.

Clockworks scores every diagnostic from 0 to 10 in three groups:

  • Energy. Anything with a metered cost, such as electricity, natural gas, or chilled water.
  • Comfort. How far the space is from what the unit is supposed to deliver, such as temperature or humidity.
  • Maintenance. Wear on the equipment, such as a compressor turning on and off too often or a dirty filter.

Watch this moment in the webinar — 38:35

Michael described the usual morning for a K-12 facilities team: the first two hours go to checking complaints and alarms and building a list for the day. With Clockworks the ranked list is already there when they arrive. Service providers use the same approach to find problems first and fix them once.

How does a district know the repair worked?

The data that found the fault also shows whether it went away. Michael, speaking as a service provider, said that holds his own team to account. If Gardiner says a problem is fixed and the data shows it is still there, the K-12 facilities team has the proof.

“You’re creating kind of an accountability feedback loop.”

Watch this moment in the webinar — 43:01

Clockworks dashboards track savings two ways. Opportunity savings are faults that are still happening. Captured savings are faults that were found and fixed. Both can be viewed for a whole district, one school, or one unit, and shared with other teams.

Watch this moment in the webinar — 36:46

Thomas added that Clockworks can send tasks, with the plain-language summary, into the work order system a district already uses.

Why can a K-12 facilities team trust the numbers?

Every dollar figure in this example comes from the equipment’s own data. Michael explained where the $278 came from. Clockworks knows which coil was open and making temperature it should not have, and “that takes energy to create”.

Watch this moment in the webinar — 20:32

Behind that is the Clockworks information model, one standard way of modeling each piece of equipment and how it connects to the rest of the system. Michael called the result of setup “the digital model of the equipment”. The same model and the same 50+ expert systems run across the 4,300 buildings Clockworks monitors, so every school is analyzed the same way.

How long does it take to get started?

Setup begins with mapping the points in the BAS. Michael explained that AI takes the first pass at naming and mapping them, and a person reviews the results.

“we typically go from the first day we connect to your data to usable information in an average of thirty days.”

Watch this moment in the webinar — 53:29

He put the usual range at thirty to forty-five days, depending on the site. Thomas suggested that K-12 facilities teams start with one or two buildings to prove the return before adding more.

Bring K-12 facilities data to the budget table

Watch the full webinar above. To see what Clockworks would find in your own schools, request a demo. If you are a service provider, learn more about the Clockworks partner program.

Frequently asked questions

What is FDD for K-12 facilities?

Fault detection and diagnostics (FDD) is software that reads the data a school’s building automation system already produces and finds equipment problems, their causes, and their cost. For K-12 facilities teams, it creates a ranked list of what to fix and gives finance and leadership the numbers behind each request.

Can FDD find problems that never trigger a BAS alarm?

Yes. In the webinar example, an air handler at a high school was heating and cooling at the same time while still meeting its 55-degree setpoint. No alarm went off, and Clockworks showed $278 of waste over seven days.

How does FDD help a K-12 facilities team ask for budget?

Each diagnostic shows what a fault has cost so far and what fixing it would save over the next year. The team can show the payback on one repair, then add up the same fault across buildings to make a district-wide case.

How long does it take to get FDD running in a school district?

Michael Mandilakis of Gardiner said his team typically goes from the first data connection to usable information in about thirty days, with a usual range of thirty to forty-five days. Many districts start with one or two buildings.

Back to blog